Project Description

J-Series Wall Mounted

ARV DC Inverter VRF

ARV6 Outdoor unit Full DC Inverter series offer the latest in VRF design. It is a modern yet compact 2019 designed low noise series, coming at capacities starting from 8 ~ 16 kW and 22 ~ 26 for mini, unitary series and 25 to 61,5 kW for the modular type, to up to 90kW for non-modular big capacity single platforms.

Special Features

ENERGY EFFICIENCY

A Leading IPLV performance of up to 6,17, EER 4,75 and COP 5,48 are values achieved by using all energy efficiency technologies available today, such as the latest generation EVI ALL DC Inverter compressor, brushless DC Fan motors and a highly efficient e-Pass condenser and plate heat exchanger.

ALL DCI Outdoor

ARV6 Outdoor units are equipped with full DC Inverter technology only. DC Inverter compressors are combined with brushless DC fan motors, bringing better control and lower consumption under all conditions.

High pressure Chamber Compressor

ARV III comes with a specially designed Enhanced Vapor injection high pressure chamber scroll compressor designed in Japan. The compressor is driven by 180 a sine wave control logic delivering brilliant results.

3-Step Sub cooling technologies

An S circuit design heat exchanger built with fish type fins and inner groove, together with a unique AUX two-to-one refrigerant flow design and a sub-cooling plate heat exchanger, all improve heat exchange efficiency.

Twin EXV design

The twin EXV system assures precise load and temperature control, increasing efficiency and user comfort.

Unique oil balance technology

AUX has designed a unique oil balance technology logic, free from extra oil piping.

Backup technology

Compressor, fan motor and module backup logic allows minimum downtime. Random sequence technology operates units and compressors in turn.

Installation convenience

Non polar wires, auto addressing, auto ref charge technology, and black box function are some of the various installation advantages of ARV6

Specifications

Model ARVWM-H022/R1X(J) ARVWM-H028/R1X(J) ARVWM-H036/R1X(J) ARVWM-H045/R1X(J) ARVWM-H056/R1X(J) ARVWM-H071/R1X(J)
Operation COOLING HEATING COOLING HEATING COOLING HEATING COOLING HEATING COOLING HEATING COOLING HEATING
Nominal Capacity kW 2,20 2,50 2,80 3,00 3,60 4,30 4,50 5,00 5,60 6,00 7,10 8,00
Power Input W 14,0 14,0 14,0 25,0 25,0 35,0
Power Supply V-Ph-Hz 230V ~ 1N – 50 Hz 230V ~ 1N – 50 Hz 230V ~ 1N – 50 Hz 230V ~ 1N – 50 Hz 230V ~ 1N – 50 Hz 230V ~ 1N – 50 Hz
Air Flow Volume m3/h 650/600/580 650/600/580 650/600/580 850/750/650 850/750/650 1.200/950/800
Sound Pressure Level IDU (H/M/L) – ODU. dB(A) 38 / 33 / 27 38 / 33 / 27 38 / 33 / 27 45 / 41 / 35 45 / 41 / 35 48 / 45 / 39
Diameter Liquid-Gas Connection Pipe inch 1/4″ – 3/8″ 1/4″ – 3/8″ 1/4″ – 3/8″ 1/4″ – 1/2″ 1/4″ – 1/2″ 1/4″ – 5/8″
Drain Pipe Diameter inch DN20 – 3/4″ DN20 – 3/4″ DN20 – 3/4″ DN20 – 3/4″ DN20 – 3/4″ DN20 – 3/4″
Indoor Unit Dimension LxHxD /Weight mm/kg 850x300x198 / 10 850x300x198 / 10 850x300x198 / 10 970x315x235 / 14 970x315x235 / 14 1.110x330x235 / 16

*  Colder, Average, Warmer climate zones for heating operation