Project Description
ARV Individual ODU
ARV DC Inverter VRF
ARV6 Outdoor unit Full DC Inverter series offer the latest in VRF design. It is a modern yet compact 2019 designed low noise series, coming at capacities starting from 8 ~ 16 kW and 22 ~ 26 for mini, unitary series and 25 to 61,5 kW for the modular type, to up to 90kW for non-modular big capacity single platforms.
Outdoor units
ARV6 Mini is a compact non-modular Outdoor unit series with focus on smaller size VRF applications. The outdoor unit footprint is minimal, yet powerful enough to support bigger residential or small office applications. Small in size but with all the ARV6 technological and versatility potential, Mini ARV6 is a, ideal solution.
Special Features
ENERGY EFFICIENCY
A Leading IPLV performance of up to 6,17, EER 4,75 and COP 5,48 are values achieved by using all energy efficiency technologies available today, such as the latest generation EVI ALL DC Inverter compressor, brushless DC Fan motors and a highly efficient e-Pass condenser and plate heat exchanger.
ALL DCI Outdoor
ARV6 Outdoor units are equipped with full DC Inverter technology only. DC Inverter compressors are combined with brushless DC fan motors, bringing better control and lower consumption under all conditions.
High pressure Chamber Compressor
ARV III comes with a specially designed Enhanced Vapor injection high pressure chamber scroll compressor designed in Japan. The compressor is driven by 180 a sine wave control logic delivering brilliant results.
3-Step Sub cooling technologies
An S circuit design heat exchanger built with fish type fins and inner groove, together with a unique AUX two-to-one refrigerant flow design and a sub-cooling plate heat exchanger, all improve heat exchange efficiency.
Twin EXV design
The twin EXV system assures precise load and temperature control, increasing efficiency and user comfort.
Unique oil balance technology
AUX has designed a unique oil balance technology logic, free from extra oil piping.
Backup technology
Compressor, fan motor and module backup logic allows minimum downtime. Random sequence technology operates units and compressors in turn.
Installation convenience
Non polar wires, auto addressing, auto ref charge technology, and black box function are some of the various installation advantages of ARV6
Specifications
ARV Individual ODU Panel
MODEL | ARV-H620/5R1I | ARV-H670/5R1I | ARV-H730/5R1I | ||||
Operation | COOLING | HEATING | COOLING | HEATING | COOLING | HEATING | |
Capacity | HP | 22 | 24 | 26 | |||
Capacity | kW | 61,5 | 69,0 | 67,0 | 75,0 | 73,0 | 81,5 |
Power Input (min- nom-max) | kW | 18,67 | 17,75 | 20,10 | 19,30 | 21,90 | 20,20 |
Current Input (nom) | A | 32,53 | 30,92 | 35,02 | 33,62 | 38,15 | 35,19 |
SEER – SCOP(C/A/W) – Energy Class | W/W | 3,29 | 3,89 | 3,33 | 3,89 | 3,33 | 4,03 |
Ambient Temperature Range | oC | -5 ~52℃ | -20 ~27℃ | -5 ~52℃ | -20 ~27℃ | -5 ~52℃ | -20 ~27℃ |
Power supply | V-Ph-Hz | 400V ~ 3N – 50 Hz | |||||
Compressor Type / Qty | HITACHI DC Inverter x 2 | ||||||
Fan Type / Qty | Axial Flow / AC Motor x 2 | ||||||
Sound Pressure Level ODU. | dB(A) | ≤63 | ≤63 | ≤65 | |||
Refrigerant charge | kg | R410a – | R410a – | R410a – | |||
Diameter Liquid-Gas Connection Pipe | mm | 15,88 / 28,6 | 15,88 / 28,6 | 19,05 / 34,9 | |||
Max IDU Units | pcs | 36 | 39 | 43 | |||
Connecting Ratio | % | 50~130% | 50~130% | 50~130% | |||
Outdoor Unit Dimension LxDxH /Weight | mm/kg | 1.590 × 765 × 1.600 / 400 | 1.590 × 765 × 1.600 / 400 | 2.350 × 765 × 1.600 / 500 |
MODEL | ARV-H785/5R1I | ARV-H850/5R1I | ARV-H900/5R1I | ||||
Operation | COOLING | HEATING | COOLING | HEATING | COOLING | HEATING | |
Capacity | HP | 28 | 30 | 32 | |||
Capacity | kW | 78,5 | 87,5 | 85,0 | 95,0 | 90,0 | 100,0 |
Power Input (min- nom-max) | kW | 23,70 | 22,00 | 25,80 | 24,40 | 27,50 | 26,30 |
Current Input (nom) | A | 41,29 | 38,33 | 44,95 | 42,51 | 47,91 | 45,82 |
SEER – SCOP(C/A/W) – Energy Class | W/W | 3,31 | 3,98 | 3,29 | 3,89 | 3,27 | 3,8 |
Ambient Temperature Range | oC | -5 ~52℃ | -20 ~27℃ | -5 ~52℃ | -20 ~27℃ | -5 ~52℃ | -20 ~27℃ |
Power supply | V-Ph-Hz | 400V ~ 3N – 50 Hz | |||||
Compressor Type / Qty | HITACHI DC Inverter x 2 | ||||||
Fan Type / Qty | Axial Flow / AC Motor x 2 | ||||||
Sound Pressure Level ODU. | dB(A) | ≤65 | ≤65 | ≤65 | |||
Refrigerant charge | kg | R410a – | R410a – | R410a – | |||
Diameter Liquid-Gas Connection Pipe | mm | 19,05 / 34,9 | 19,05 / 34,9 | 19,05 / 34,9 | |||
Max IDU Units | pcs | 46 | 50 | 53 | |||
Connecting Ratio | % | 50~130% | 50~130% | 50~130% | |||
Outdoor Unit Dimension LxDxH /Weight | mm/kg | 2.350 × 765 × 1.600 / 500 | 2.350 × 765 × 1.600 / 500 | 2.350 × 765 × 1.600 / 500 |
* Colder, Average, Warmer climate zones for heating operation